Hi,
how is calculate inner level arm for shear PSC design? on manual is 0.9d, but how is calculte d if there isn't longitudinal reinforcement ? which rule it used in case there are only tendon in a differents layer position?
thanks
regards
carlo
Answer:
Dear Carlo,
The lever arm is calculated from the ultimate bending analysis:
Kindly let us know if further assistance is required.
B Swapnil Agarwal
Technical Support Engineer

Click here to give FEEDBACK
Dear Carlo,
As per the Euro 1992 -1-1 6.2.3 the parameter z is the lever arm in the bending moment calculation, but if we don't have accurate calculations it is suggested to take 0.9*d .
This has been improved in the midas civil 2020 v2.1 where we calculate the lever arm exactly as per the moment capacity and the compressive force in the section as shown below:
We are attaching the excel sheet for your reference.
B Swapnil Agarwal
Technical Support Engineer

Click here to give FEEDBACK