How to create separate load factors for UDL and Axle load of moving load for combinations?

Question:
In the frequent load combination, I would like to apply 0,75*MV (axle) and 0,4*MV (UDL).  In the quasi-permanent load combinations for Finland, I need to apply 0,4*MV (UDL) only.  How can I verify this in my combinations/ design/ results?
Answer:
For a given MVL Case the psi factors are either applied for both the Tandem System and the UDL, or for neither. This is controlled from the MVL Case definition:

In order to apply different factors for different combinations you will need to define different load cases. In the example you have given, you will need to define two different vehicles, one where the psi factors are 0.75 and 0.4, and one where they are 0 and 0.4. Then use each vehicle in a separate load case where the psi factors are included.

You can see the factors applied to the loads using the Results >> Moving Load Tracer, where you can choose to display the loads with the psi factors or without. Note that in both cases the analysis results consider the factors if specified in the MVL Case definition, it is only the display of the load values on screen that reflects or not the psi factor:
Creation date: 10/29/2018 5:47 PM      Updated: 6/16/2023 2:26 PM
Files   
DataImage14.png
163 KB
DataImage88.png
28 KB
Kauniston kvl.mcb
928 KB