Two cell box Girder

Question:

Dear Midas 

We know that midas civil, can  check the section for torsion. Torsion reinforcement can be input in "section manager_reinforcement". 

Could you clarify, if the box is a double cell, the input is also similar ? and midas check the torsional capacity based on two cell ?

Would be very nice, if you can share any material related  to manual cross-verification of the model value.


Thanks and Regards



Answer:

Hi,

Please let me know the standard on which you want to check torsion capacity like Eurocode, AASHTO.

Regards,
DK Lee 


Thanks for reply. 

As per Eurocode. 

Regards



Hi,

I am sorry for the late response. Eurocode recommends two methods for solid cross-sections and box sections as shown below. However, only the method for solid cross-sections is implemented.  Thus, two cell box girder cannot be checked properly with midas Civil. We will try to implement the method for box section in the future release.

Regards,
DK Lee